Specifications:
Load Rating: 20 amps @ 120 volts
Power Requirement (no load): 15 watts
Surge Let-Through Voltage (6000-volt surge): 0 volts
UL 1449 Adjunct Classification Test Results:
1000 surges, 6000 volts, 3000 amps, B3 pulse.
Measured suppressed voltage: 170 volts, no failures
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load):
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load):
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current:
Unlimited, due to current limiting*
Maximum Applied Surge Energy:
Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses):
1 kV>500,000; 3 kV>10,000; 6 kV>1000
Undervoltage Shutdown: 90 volts (resume at 100 v)
Overvoltage Shutdown: 145 volts (resume at 135 v)
Maximum Load Inrush Current During Power-up:
1000 Joules
Remote Turn-on Applied Voltage Range: 5 to 30 volts DC
Remote Turn-on Current Draw:
Contact Closure: 1.5 mA
5 V DC Applied Voltage: 0.1 mA
12 V DC Applied Voltage: 1.5 mA
24 V DC Applied Voltage: 5.0 mA
Auxiliary Relay Contact Rating: 30 Volts at 1 Amp
LED Output: 12 volts DC, maximum 20 mA (resistor required)
Dimensions: 1.75" H x 19" W x 10.5" D (4.5 x 48.3 x 26.7 cm)
Weight: 11 lbs (5 kg)
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H., non-condensing
Agency Listings: ETL and cETL (UL 1449,
2nd edition; CSA C22.2 No.8-M1986, R2000)
Technical Description:
The SX1120RT shall be a one-rack-space unit in a magnetic shielding steel enclosure. It shall operate from 120 volts AC and have a 9-foot, grounded, 3-wire #12 line cord. There shall be 8 grounded AC receptacles on the back panel, with 6 switched and 2 always on. The unit shall have a front-panel courtesy receptacle and remote-control capability with a visual indicator. Overall dimensions shall be 1.75" H x 19" W x 10.5" D. Weight shall be 11 pounds.
The SX1120RT shall have a load rating of 20 amps at 120 volts, a self-test circuit with visual indicator, and provide EMI/RFI filtering, inrush current elimination and catastrophic over/under-voltage shutdown. It shall meet Federal Grade A, Class 1, Mode 1 guidelines for powerline surge suppressors and withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts.